/*! This file is auto-generated */ .wp-block-button__link{color:#fff;background-color:#32373c;border-radius:9999px;box-shadow:none;text-decoration:none;padding:calc(.667em + 2px) calc(1.333em + 2px);font-size:1.125em}.wp-block-file__button{background:#32373c;color:#fff;text-decoration:none} Problem 82 Transformers are often rated in ... [FREE SOLUTION] | 91Ó°ÊÓ

91Ó°ÊÓ

Transformers are often rated in terms of kilovolt-amps. A pole on a residential street has a transformer rated at $35 \mathrm{kV} \cdot \mathrm{A}$ to serve four homes on the strect. (a) If each home has a fuse that limits the incoming current to \(60 \mathrm{A}\) rms at \(220 \mathrm{V}\) rms, find the maximum load in \(\mathrm{kV} \cdot \mathrm{A}\) on the transformer. (b) Is the rating of the transformer adequate? (c) Explain why the transformer rating is given in kV.A rather than in kW.

Short Answer

Expert verified
Also, explain why the transformer rating is given in kVA rather than kW. #Answer: The maximum load on the transformer is approximately 52.8kVA. The transformer's rating of 35kVA is NOT adequate to handle the load, as 52.8kVA exceeds the 35kVA rating. Transformer ratings are given in kVA because transformers deal with voltages and currents, not power directly. Since the input voltage and current are directly related to the transformer's maximum load capacity, it is more appropriate to express the rating in kVA, which represents the product of voltage and current.

Step by step solution

01

Maximum load per home

Given, each home has a fuse that limits the incoming current to 60A rms at 220V rms. The maximum load each home can safely consume is given by the formula: Load (Per Home) = Voltage × Current Calculate the maximum load per home. Load (Per Home) = 220V × 60A = 13,200W
02

Total load on the transformer

There are four homes connected to the transformer. To find the total load on the transformer, add the loads of each home. Total Load = Load (Per Home) × Number of Homes Total Load = 13,200W × 4 = 52,800W = 52.8kW Now, convert this load to kVA. We know that: Power (kVA) = Power (kW) × Power Factor Assuming a power factor of 1 (which is the maximum possible value). Total Load (kVA) ≈ 52.8kVA (Approximated as the power factor is not provided).
03

Checking the adequacy of the transformer rating

The rating of the transformer is given as 35 kVâ‹…A. Compare the total load on the transformer to its rating. Total Load (kVA) = 52.8kVA Transformer Rating = 35kVA Since the total load (52.8kVA) exceeds the transformer rating (35kVA), the transformer is NOT adequate to handle the load.
04

Explain why the transformer rating is given in kVâ‹…A rather than kW.

Transformer ratings are given in kVA because transformers deal with voltages and currents, not power directly. In an AC circuit, the power is given as: Power (kW) = Voltage (V) × Current (A) × Power Factor The power factor is a measure of how efficiently the input power is converted into useful output power. The power factor ranges between 0 and 1, with 1 representing the most efficient conversion. Since the input voltage and current are directly related to the transformer's maximum load capacity, it is more appropriate to express the rating in kVA, which represents the product of voltage and current.

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with 91Ó°ÊÓ!

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

An alternator supplics a peak current of \(4.68 \mathrm{A}\) to a coil with a negligibly small internal resistance. The voltage of the alternator is \(420-\mathrm{V}\) peak at \(60.0 \mathrm{Hz}\) When a capacitor of $38.0 \mu \mathrm{F}$ is placed in series with the coil, the power factor is found to be \(1.00 .\) Find (a) the inductive reactance of the coil and (b) the inductance of the coil.
Suppose that an ideal capacitor and an ideal inductor are connected in series in an ac circuit. (a) What is the phase difference between \(v_{\mathrm{C}}(t)\) and \(v_{\mathrm{L}}(t) ?\) [Hint: since they are in series, the same current \(i(t)\) flows through both. \(]\) (b) If the rms voltages across the capacitor and inductor are \(5.0 \mathrm{V}\) and \(1.0 \mathrm{V}\), respectively, what would an ac voltmeter (which reads rms voltages) connected across the series combination read?
In the crossover network of Problem \(61,\) the inductance \(L\) is $1.20 \mathrm{mH}$. The capacitor is variable; its capacitance can be adjusted to set the crossover point according to the frequency response of the woofer and tweeter. What should the capacitance be set to for a crossover point of $180 \mathrm{Hz} ?[\text {Hint}:$ At the crossover point, the currents are equal in amplitude. \(]\)
An ac circuit has a single resistor, capacitor, and inductor in series. The circuit uses \(100 \mathrm{W}\) of power and draws a maximum rms current of $2.0 \mathrm{A}\( when operating at \)60 \mathrm{Hz}\( and \)120 \mathrm{V}$ rms. The capacitive reactance is 0.50 times the inductive reactance. (a) Find the phase angle. (b) Find the values of the resistor, the inductor, and the capacitor.
(a) What mas current is drawn by a \(4200-\mathrm{W}\) electric room heater when running on \(120 \mathrm{V}\) rms? (b) What is the power dissipation by the heater if the voltage drops to \(105 \mathrm{V}\) rms during a brownout? Assume the resistance stays the same.
See all solutions

Recommended explanations on Physics Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.