/*! This file is auto-generated */ .wp-block-button__link{color:#fff;background-color:#32373c;border-radius:9999px;box-shadow:none;text-decoration:none;padding:calc(.667em + 2px) calc(1.333em + 2px);font-size:1.125em}.wp-block-file__button{background:#32373c;color:#fff;text-decoration:none} Problem 72 A \(60 . \mathrm{Hz}\) 20-kVA \(... [FREE SOLUTION] | 91Ó°ÊÓ

91Ó°ÊÓ

A \(60 . \mathrm{Hz}\) 20-kVA \(8000 / 240\) -V-rms trans former has the following equivalent-circuit parameters: $$\begin{array}{lcl} \hline \text { Primary resistance } & R_{1} & 15 \Omega \\ \text { Secondary resistance } & R_{2} & 0.02 \Omega \\ \text { Primary leakage reactance } & X_{1}=\omega L_{1} & 120 \Omega \\ \text { Secondary leakage reactance } & X_{2}=a b_{-2} & 0.15 \Omega \\ \text { Magnetizing reactance } & X_{m}=\omega I_{m} & 30 \mathrm{k} \Omega \\\ \text { Core-loss resistance } & R_{c} & 200 \mathrm{k} \Omega \\ \hline \end{array}$$ Find the percentage regulation and power efficiency for the transformer for a rated load having a lagging power factor of 0.8

Short Answer

Expert verified
Voltage regulation is 1.577%. Efficiency is 97.98%.

Step by step solution

01

Calculate the Turns Ratio

The turns ratio, \( a \), of a transformer is the ratio of primary voltage to secondary voltage. We can calculate it using the equation: \[ a = \frac{V_{primary}}{V_{secondary}} = \frac{8000}{240} = 33.33 \] This ratio will be used to refer all secondary parameters to the primary side.
02

Refer Secondary Parameters to Primary Side

For referring the secondary values to the primary side, the impedance and resistance of the secondary are multiplied by \( a^2 \). Therefore,For secondary resistance:\[ R_{2}' = R_{2} \times a^2 = 0.02 \times (33.33)^2 = 22.22 \Omega \]For secondary leakage reactance:\[ X_{2}' = X_{2} \times a^2 = 0.15 \times (33.33)^2 = 50.00 \Omega \]
03

Calculate Total Equivalent Impedance (Referred to Primary)

The equivalent resistance (R_{eq}) and reactance (X_{eq}) can now be calculated by summing the primary and referred secondary values:\[ R_{eq} = R_{1} + R_{2}' = 15 + 22.22 = 37.22 \Omega \]\[ X_{eq} = X_{1} + X_{2}' = 120 + 50 = 170 \Omega \]
04

Calculate Load Power and Current

The apparent power at the secondary side is given by the power rating: 20 kVA. Load current on the secondary side can be calculated using: \[ I_2 = \frac{S}{V_{secondary}} = \frac{20000}{240} \approx 83.33 \, \text{A} \]Current referred to primary:\[ I_1 = \frac{I_2}{a} = \frac{83.33}{33.33} \approx 2.5 \, \text{A} \]
05

Calculate Percentage Regulation

The voltage regulation is given as:\[ \text{Regulation} = \frac{(R_{eq} \cdot I_1 \cdot \cos \phi + X_{eq} \cdot I_1 \cdot \sin \phi)}{V_1} \times 100 \]Where \( \cos \phi = 0.8 \) (lagging power factor), \( \sin \phi = \sqrt{1 - (\cos \phi)^2} = 0.6 \).Using these values:\[ \text{Regulation} \approx \frac{(37.22 \cdot 2.5 \cdot 0.8 + 170 \cdot 2.5 \cdot 0.6)}{8000} \times 100 \approx 1.577\% \]
06

Calculate Power Efficiency of Transformer

The efficiency of a transformer is given by the formula:\[ \text{Efficiency} = \frac{\text{Output Power}}{\text{Output Power} + \text{Losses}} \times 100 \]Where losses include copper loss and core loss. Copper loss = \( I_1^2 (R_{1} + R_{2}') \) and core loss = \( \frac{V_1^2}{R_c} \).\[ \text{Copper Loss} = 2.5^2 \times 37.22 = 232.625 \, \text{W} \]\[ \text{Core Loss} = \frac{8000^2}{200000} = 320 \, \text{W} \]The Output Power = 0.8 \times 20000 = 16000 W (since it's lagging power factor).\[ \text{Efficiency} = \frac{16000}{16000 + 232.625 + 320} \times 100 \approx 97.98\% \]

Unlock Step-by-Step Solutions & Ace Your Exams!

  • Full Textbook Solutions

    Get detailed explanations and key concepts

  • Unlimited Al creation

    Al flashcards, explanations, exams and more...

  • Ads-free access

    To over 500 millions flashcards

  • Money-back guarantee

    We refund you if you fail your exam.

Over 30 million students worldwide already upgrade their learning with 91Ó°ÊÓ!

Key Concepts

These are the key concepts you need to understand to accurately answer the question.

Turns Ratio Calculation
When studying electrical transformers, one of the key aspects is understanding the turns ratio. This is crucial because it defines how the voltage is transformed between the primary and secondary coils. The turns ratio, denoted as \( a \), is computed by dividing the primary voltage by the secondary voltage: \[ a = \frac{V_{primary}}{V_{secondary}} \]For our scenario, involving a transformer with primary and secondary voltages of 8000 V and 240 V respectively, the turns ratio is calculated as:\[ a = \frac{8000}{240} = 33.33 \] This means that the primary voltage is 33.33 times that of the secondary. This ratio helps in referring secondary parameters (like impedance) to the primary side, making calculations more manageable.To convert secondary parameters to primary, you multiply them by \( a^2 \). This ensures compatibility and consistency in your calculations. It's an essential part of transformer analysis as it helps in estimating equivalent circuit parameters accurately.
Voltage Regulation
Voltage regulation in transformers indicates the capability of the transformer to provide a constant output voltage despite variations in load current. It is important because it reflects how well a transformer maintains voltage levels under different loading conditions.We calculate voltage regulation using the formula:\[ \text{Regulation} = \frac{(R_{eq} \cdot I_1 \cdot \cos \phi + X_{eq} \cdot I_1 \cdot \sin \phi)}{V_1} \times 100 \]Here, \( R_{eq} \) is the equivalent resistance, \( X_{eq} \) is the equivalent reactance, \( I_1 \) is the current referred to the primary, and \( \cos \phi \) represents the power factor (lagging in this case). The sine component \( \sin \phi \) is derived as \( \sqrt{1 - (\cos \phi)^2} \).In our example, with a lagging power factor of 0.8, the voltage regulation comes out to be approximately 1.577%. This result demonstrates that the voltage at the secondary side falls by 1.577% from no-load to full-load condition. A lower percentage of regulation indicates better performance regarding voltage consistency.
Power Efficiency
Understanding power efficiency in transformers is vital for ensuring optimal performance. Efficiency depicts how effectively a transformer transfers electrical power from the primary to the secondary side without excessive energy loss.Calculate efficiency with the formula:\[ \text{Efficiency} = \frac{\text{Output Power}}{\text{Output Power} + \text{Losses}} \times 100 \]Losses primarily consist of copper and core losses. Copper loss occurs due to resistance in the windings and is calculated by \( I_1^2 (R_{1} + R_{2}') \), whereas core loss arises from magnetic properties and is \( \frac{V_1^2}{R_c} \).In this particular transformer, it handles a load with a lagging power factor of 0.8, resulting in an output power of 16000 W. Combining copper and core losses of 232.625 W and 320 W respectively, the transformer exhibits an efficiency of approximately 97.98%. Thus, nearly 98% of the input power is effectively converted to useful output, signifying a high-performing transformer with minimal losses.

One App. One Place for Learning.

All the tools & learning materials you need for study success - in one app.

Get started for free

Most popular questions from this chapter

A relay has a 500 -turn coil that draws \(50 \mathrm{mA}\) rms when a \(60 . \mathrm{Hz}\) voltage of \(24 \mathrm{V} \mathrm{rms}\) is applied. Assume that the resistance of the coil is negligible, Determine the peak flux linking the coil, the reluctance of the core, and the inductance of the coil.

We have a transformer designed to operate at \(60 \mathrm{Hz}\). The voltage ratings are 4800 \(\mathrm{V} \mathrm{rms}\) and \(240 \mathrm{V} \mathrm{rms}\) for the primary and secondary windings, respectively. The transformer is rated for \(10 \mathrm{kVA}\). Now, we want to use this transformer at \(120 \mathrm{Hz}\) Discuss the factors that must be considered in setting ratings appropriate for operation at the new frequency. (Keep in mind that for best utilization of the material in the transformer. we want the peak flux density to be nearly at saturation for both frequencies

A uniform flux density of 1 T is perpendicular to the plane of a five-turn circular coil of radius \(10 \mathrm{cm} .\) Find the flux linking the coil and the flux linkages. Suppose that the field is decreased to zero at a uniform rate in \(1 \mathrm{ms}\) Find the magnitude of the voltage induced in the coil.

Sketch the \(B-H\) curve for a magnetic material such as iron. Show hysteresis and saturation

What are two causes of core loss for a coil with an iron core excited by an ac current? What considerations are important in minimizing loss due to each of these causes? What happens to the power loss in each case if the frequency of operation is doubled while maintaining constant peak flux density?

See all solutions

Recommended explanations on Physics Textbooks

View all explanations

What do you think about this solution?

We value your feedback to improve our textbook solutions.

Study anywhere. Anytime. Across all devices.